Thermodynamic performance of an ejector-compressor enhanced diffusion-absorption refrigeration system for cement kiln waste heat recovery

Bisulandu, Baby-Jean Robert Mungyeko, Mboko, Marcel Tsimba, Mbozi, Lucien Mbozi, Rousse, Daniel R. et Ilinca, Adrian. 2026. « Thermodynamic performance of an ejector-compressor enhanced diffusion-absorption refrigeration system for cement kiln waste heat recovery ». Transactions of the Canadian Society for Mechanical Engineering, vol. 50.

[thumbnail of Rousse-D-2026-33806.pdf]
Prévisualisation
PDF
Rousse-D-2026-33806.pdf - Version publiée
Licence d'utilisation : Creative Commons CC BY.

Télécharger (1MB) | Prévisualisation

Résumé

The growing scarcity and rising costs of fossil fuels are accelerating the global transition toward energy-efficient, low-emission industrial systems. Cement plants reject large amounts of thermal energy through exhaust gases, offering an opportunity for heat recovery. This study investigates the thermodynamic performance of a diffusion–absorption refrigeration (DAR) system enhanced with an ejector and a compressor (DAR-EC) and powered by residual heat from a cement kiln. The system is modelled using the M2EP framework (mass, energy, exergy, and performance) and optimized through a particle swarm algorithm. The particle swarm optimization algorithm identifies optimal pressure and concentration levels that maximize coefficient of performance, subject to constraints on the low-temperature heat source. The working fluid is a ternary H2O–NH3–H2 mixture, enabling continuous circulation between the evaporator and absorber. Integrating the ejector and compressor increases the operating pressure at the evaporator outlet and the absorber inlet, thereby improving cycle performance. A sensitivity analysis to temperature, concentration, and pressure variations is performed. Results show that the DAR-EC configuration significantly increases the cooling capacity and raises the coefficient of performance from 0.27 (DAR) to 0.49 (DAR-EC). Exergy analysis additionally reveals that generator and absorber irreversibilities dominate system losses. The model is validated against published data and demonstrates its suitability for industrial heat-recovery applications. The findings provide a decision-support basis for implementing DAR-EC systems to valorize waste heat. Given that this model uses a water-ammonia mixture, the heat source temperature must be between 80 and 200 °C.

Type de document: Article publié dans une revue, révisé par les pairs
Chercheur(-euse):
Chercheur(-euse)
Rousse, Daniel R.
Ilinca, Adrian
Affiliation: Génie mécanique, Génie mécanique
Date de dépôt: 15 juin 2026 19:31
Dernière modification: 28 sept. 2026 13:00
URI: https://espace2.etsmtl.ca/id/eprint/33806

Actions (Authentification requise)

Dernière vérification avant le dépôt Dernière vérification avant le dépôt